01 / Direct answerChoose the smallest model that passes both the energy and current checks for the complete system.
The search question is: which 25.6V LiFePO4 battery is better—60Ah, 100Ah, 150Ah or 200Ah? In SAVYEN's published large-case range, the four models store 1.536 kWh, 2.56 kWh, 3.84 kWh and 5.12 kWh of nominal energy respectively. A larger Ah rating provides more nominal energy, but capacity alone does not prove inverter, charger or load compatibility.
Published maximum continuous discharge rises from 50 A for the 60 Ah model to 100 A for the 100 Ah model and 150 A for both the 150 Ah and 200 Ah models. The 200 Ah model adds energy over the 150 Ah model, not a higher published continuous-current limit. Verify energy, continuous current, surge, charging, voltage range, installation space, mass, cabling and protection before selecting a model.
60 Ah
1.536 kWh nominal; 50 A maximum continuous discharge; 525 × 243 × 226 mm; 11.88 kg net.
100 Ah
2.56 kWh nominal; 100 A maximum continuous discharge; 525 × 243 × 226 mm; 18.77 kg net.
150 Ah
3.84 kWh nominal; 150 A maximum continuous discharge; 525 × 267 × 225 mm; 22.54 kg net.
200 Ah
5.12 kWh nominal; 150 A maximum continuous discharge; 525 × 267 × 225 mm; 26.36 kg net.
02 / Energy calculationConvert amp-hours to kWh before comparing backup time.
Nominal energy equals nominal voltage × capacity ÷ 1,000. At 25.6 V, the calculations are 25.6 × 60 ÷ 1,000 = 1.536 kWh, 25.6 × 100 ÷ 1,000 = 2.56 kWh, 25.6 × 150 ÷ 1,000 = 3.84 kWh and 25.6 × 200 ÷ 1,000 = 5.12 kWh.
At a constant 1 kW load, nominal energy ÷ load gives theoretical nameplate runtimes of 1.536, 2.56, 3.84 and 5.12 hours. Actual AC runtime is lower after the permitted operating window, inverter losses, standby use, wiring, temperature, ageing and reserve are included. These simple calculations are comparisons, not runtime guarantees.
Capacity increase
Relative to 60 Ah, nominal energy is 66.7% higher at 100 Ah, 150% higher at 150 Ah and 233.3% higher at 200 Ah.
Size from a load schedule
Add the watt-hours required during the backup period, then use confirmed usable-energy and efficiency values. Do not use peak watts alone to size energy.
03 / Current and surgeBattery power is limited by current as well as stored energy.
At the 25.6 V nominal voltage, the published continuous-current limits correspond to simple DC power products of 1.28 kW at 50 A, 2.56 kW at 100 A and 3.84 kW at 150 A. These are not AC output approvals: battery voltage changes during operation, and inverter losses, duration, BMS behavior and environmental conditions affect the permissible load.
The product data lists instantaneous discharge of 100 A, 200 A, 300 A and 300 A for the 60 Ah through 200 Ah models. Instantaneous current is not a continuous rating and does not by itself confirm motor, pump or inverter surge compatibility. Obtain the permitted duration and complete protection design in writing.
First-pass current formula
Estimated battery current = AC load watts ÷ (battery voltage × inverter efficiency). Use actual equipment values for final engineering.
Do not infer power from Ah
The 150 Ah and 200 Ah models share the same published 150 A continuous limit, even though the 200 Ah model stores 33.3% more nominal energy.
04 / ChargingMatch the charger profile and current to the selected model.
The complete series is published at 25.6 V nominal with a 29.2 V charging cut-off and 20 V discharge cut-off. The listed standard charging-current limits are 25 A or less for 60 Ah, 50 A or less for 100 Ah and 75 A or less for both 150 Ah and 200 Ah.
Confirm that the inverter or charger can use the required LiFePO4 voltage profile and that its current, temperature behavior and protective settings match the ordered battery. A device being marketed for a 24 V-class battery does not establish compatibility with every 25.6 V LiFePO4 model.
Temperature
Published charging temperature is 0-45°C and discharge temperature is -20-65°C; the final enclosure and installation still require environmental review.
Monitoring
The product data lists an LCD display and Bluetooth for the series. Bluetooth monitoring is not evidence of inverter communication-protocol compatibility.
05 / InstallationCheck enclosure, handling and series design before ordering.
The 60 Ah and 100 Ah models use the published 525 × 243 × 226 mm enclosure, while the 150 Ah and 200 Ah models use 525 × 267 × 225 mm. Net mass ranges from 11.88 kg to 26.36 kg. Measure clearances for terminals, cables, protection, restraint, airflow and service access rather than assuming all four capacities occupy the same space.
The product sheet states support for two units in series. Series connection raises system voltage, so the inverter, charger, disconnects and protective devices must match the complete string. Use matched batteries and obtain written confirmation for balancing, state of charge, cabling, commissioning and the exact ordered configuration.
Do not mix capacities
Do not combine 60 Ah, 100 Ah, 150 Ah and 200 Ah models in one string unless SAVYEN approves the complete design in writing.
Natural cooling
Natural cooling is listed for the range, but the installation still needs the clearances and ambient conditions required by the confirmed design.
06 / Selection checklistSend the load, equipment model and installation details for a written match.
Provide the appliance energy schedule, maximum continuous load, surge power and duration, required backup time, inverter or charger brand and exact model, installation dimensions, temperature range, destination country, quantity and any proposed series arrangement.
Ask SAVYEN to confirm the selected model, charging profile, usable-energy basis, continuous and instantaneous current conditions, BMS protection, cable and overcurrent protection, accessories and monitoring. The public product data used here does not publish cycle life, certification or warranty claims for this series, so this guide does not invent them.
Choose 60 Ah when
1.536 kWh and the 50 A limit pass every verified requirement and lower mass is important.
Choose 100 Ah when
2.56 kWh and the 100 A limit fit the load, charging and installation checks.
Choose 150 Ah when
3.84 kWh and 150 A meet the project without the extra energy and mass of 200 Ah.
Choose 200 Ah when
5.12 kWh is required and the unchanged 150 A continuous-current limit still passes.
SOURCESProduct data and related evidence.
Use these public sources to verify the model facts used in this guide. Final order specifications still require written confirmation.