LiFePO4 battery sizing guide

How to Size a LiFePO4 Battery for a Solar System

Calculate LiFePO4 battery capacity from load power, backup hours, usable fraction and inverter efficiency, then verify current and compatibility.

Last reviewed: 9 November 2026 · Technical content reviewed for public accuracy

01 / Direct answer

Divide the required load energy by the confirmed usable battery fraction and system efficiency.

The search question is: how many kWh of LiFePO4 battery does a solar system need? First calculate the energy the protected loads will use. Then convert that AC-load energy into nominal battery energy with this planning formula: nominal battery kWh = load kWh ÷ (usable battery fraction × inverter efficiency).

For example, a 1 kW average essential load running for four hours uses 4 kWh. If a preliminary design assumes an 80% usable fraction and 90% inverter efficiency, the nominal target is 4 ÷ (0.80 × 0.90) = 5.56 kWh. Those percentages are visible planning assumptions, not SAVYEN product guarantees; replace them with the limits and efficiency data confirmed for the exact battery and inverter.

Short answer

Calculate load kWh, divide by confirmed usable fraction and efficiency, add a justified reserve, then select the next practical battery configuration that also meets current and compatibility limits.

Do not size from inverter kW alone

Inverter kW describes power. Battery kWh describes stored energy. A 5 kW inverter does not automatically require or provide five hours from a 5 kWh battery.

02 / Load energy

Build an essential-load schedule before choosing a battery model.

For each protected appliance, multiply running power in kW by operating time in hours. Add the results. Use a measured load profile where possible and a realistic duty cycle for refrigerators, pumps, air conditioners and other equipment that cycles rather than running continuously.

Separate normal running energy from starting surge. Surge changes the instantaneous power and current requirement, while the operating schedule determines energy. Both must be checked, but they are not interchangeable.

Worked load schedule

Lights: 0.20 kW × 5 h = 1.00 kWh. Refrigerator average: 0.15 kW × 10 h = 1.50 kWh. Electronics: 0.10 kW × 5 h = 0.50 kWh. Total load energy = 3.00 kWh.

Average versus peak

An average-energy calculation can hide a short high-power event. Record motor starts and simultaneous loads for inverter and battery-current checks.

Backup window

Define whether the target is a four-hour outage, overnight autonomy or a full off-grid day. The same equipment needs different battery energy for each window.

03 / Nominal capacity

Convert the energy target into kWh and Ah without treating nameplate energy as delivered AC energy.

Battery energy is calculated from nominal voltage and amp-hours: nominal kWh = V × Ah ÷ 1,000. SAVYEN's published 51.2 V models therefore include 5.12 kWh at 100 Ah, 10.24 kWh at 200 Ah and 16.076 kWh at 314 Ah.

These are rated-energy values. The energy delivered to AC loads can be lower because the permitted operating window, inverter conversion, cabling, temperature, ageing, standby consumption and protection settings affect the result. Confirm the usable basis for the exact quotation rather than applying one percentage to every model.

3 kWh load example

Using illustrative assumptions of 80% usable fraction and 90% inverter efficiency: 3 ÷ (0.80 × 0.90) = 4.17 kWh nominal before any additional reserve.

8 kWh load example

Using the same illustrative assumptions: 8 ÷ (0.80 × 0.90) = 11.11 kWh nominal. This exceeds one 10.24 kWh nameplate battery, so a larger or parallel configuration would need model-level confirmation.

Ah conversion

After the voltage platform is fixed, Ah = nominal Wh ÷ nominal V. Do not compare Ah across 12.8 V, 25.6 V and 51.2 V batteries without converting to energy.

04 / Power and current

Verify that the selected battery can supply the load as well as store enough energy.

A first-pass DC-current estimate is inverter output power ÷ (battery voltage × inverter efficiency). At 5 kW, 51.2 V and an illustrative 90% efficiency, the estimate is 5,000 ÷ (51.2 × 0.90) = approximately 108.5 A. This is a planning estimate, not an equipment rating.

Compare the result with the exact battery's continuous and peak limits, the inverter's DC demand, cable and protective-device ratings, and any derating conditions. The published 51.2 V 100 Ah product lists a 100 A maximum discharge current, while the 51.2 V 200 Ah product lists 200 A maximum continuous discharge at its stated temperature condition. Those facts do not by themselves approve either model for a specific inverter or surge profile.

Continuous load

Check the expected worst-case sustained DC current, not only the average energy use.

Starting surge

Motors, compressors and pumps may demand a short surge. Confirm the inverter and battery limits and duration on the same basis.

Parallel systems

Use only model-approved parallel quantities, matched units, equal-current cabling, suitable protection and the manufacturer's commissioning procedure.

05 / Solar recharge

Check whether the PV array can replace the energy used during the backup period.

Battery sizing and solar-array sizing are related but separate. The battery must cover the required load energy and power. The PV array must serve daytime loads and provide enough additional energy to recharge the battery under the site's solar resource and system losses.

A larger battery does not solve an undersized PV array. For an off-grid or frequently cycled system, review seasonal solar hours, weather variability, recharge time, generator or grid support and the charge-current limits of the battery and inverter.

Energy balance

Estimate daily load kWh, available PV energy and conversion losses across the relevant season rather than relying on panel wattage alone.

Recharge deadline

Define whether the battery must recover in one solar day, over several days or with grid or generator assistance.

06 / Final selection

Confirm the complete battery-and-inverter system before ordering.

Send the load schedule, maximum simultaneous power, surge loads, backup target, inverter brand and exact model, destination country, site conditions, quantity and expansion plan. Ask for written confirmation of the selected battery model, usable-energy basis, current limits, communication protocol, operating settings, included accessories and parallel architecture.

Voltage class alone does not prove compatibility. CAN and RS485 name communication methods, but the protocol, firmware, cable pinout and inverter settings must match the exact battery-and-inverter pair.

Electrical inputs

Load kW, load kWh, surge, backup hours, inverter model, voltage platform and recharge source.

Site inputs

Temperature, indoor or outdoor location, altitude, dust, humidity, cable distance and available installation space.

Commercial inputs

Quantity, destination, delivery term, required documentation, OEM needs and future expansion plan.

SOURCES

Product data and related evidence.

Use these public sources to verify the model facts used in this guide. Final order specifications still require written confirmation.

SAVYEN LiFePO4 battery range

Open source →

SAVYEN 51.2 V 100 Ah battery data

Open source →

SAVYEN 51.2 V 200 Ah battery data

Open source →

SAVYEN 51.2 V 314 Ah battery data

Open source →

SAVYEN technical content methodology

Open source →

Sizing comparison

Match the nominal-energy target to a published battery class.

The examples below compare nameplate energy only. They do not confirm usable energy, runtime, inverter compatibility, current capability or the final number of batteries.

Published battery classNominal energySizing evidence to confirm
51.2 V 100 Ah wall battery5.12 kWhUsable-energy basis, 100 A published maximum discharge, inverter protocol and surge
51.2 V 200 Ah floor battery10.24 kWhUsable-energy basis, 200 A published continuous limit conditions, parallel design and protocol
51.2 V 314 Ah floor battery16.076 kWhUsable-energy basis, rated current conditions, parallel design, protocol and installation
Larger or parallel configurationProject-specificExact matched units, current sharing, protection, cabling, controls and commissioning

Use the formula to establish a target, then ask SAVYEN to confirm the exact model and architecture from the real load, inverter and site information.

Request a Like-for-Like Quote →

Practical answers

Questions buyers ask before ordering.

How do I calculate LiFePO4 battery size for a solar system?

Calculate load energy in kWh, then divide it by the confirmed usable battery fraction and inverter efficiency. Add only a justified reserve, select a practical battery configuration and verify current, surge, voltage, communication and recharge capacity.

How much battery do I need for a 1 kW load for five hours?

The load uses 5 kWh. With illustrative assumptions of 80% usable fraction and 90% efficiency, the nominal target is 5 ÷ (0.80 × 0.90) = 6.94 kWh before any additional reserve. Replace those assumptions with confirmed equipment data.

How long will a 5.12 kWh LiFePO4 battery run a home?

There is no universal runtime. Theoretical nameplate runtime is 5.12 kWh divided by average load kW, but actual AC runtime also depends on the permitted operating window, inverter efficiency, standby use, current limits and reserve. A 1 kW load therefore does not automatically receive 5.12 hours.

Is one 10.24 kWh battery enough for 8 kWh of AC load energy?

Not under the illustrative 80% usable and 90% efficiency assumptions, which require 11.11 kWh nominal before extra reserve. The actual answer depends on the confirmed usable-energy and efficiency basis for the selected equipment.

Can I size the battery from inverter power?

No. Inverter kW is a power rating, while battery kWh is energy. Use the load schedule and backup hours for energy, then use inverter power and surge to verify battery current capability.

Should battery capacity match solar-panel capacity?

No fixed one-to-one ratio applies. Size battery energy from the load and backup target; size the PV array from daily energy demand, local solar resource, conversion losses and the required recharge time.

FACTORY PROJECT SUPPORT

Send the load, country and backup target.

We will match the inverter, LiFePO4 battery and solar array for technical confirmation.

Request a Proposal →